Electric Power:

Cat XLM Switchgear

Cat XLM Switchgear
Configuration
Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV
Operating Temperature
0 degrees to 50 degrees C

The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications.



Product Specs

  • Technical Summary

  • Configuration
    Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
    Modes of Operation
    Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
    Application
    LV and MV ( 208V - 38 kV
    Configuration
    Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
    Modes of Operation
    Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
    Application
    LV and MV ( 208V - 38 kV
  • Environmental Parameters

  • Operating Temperature
    0 degrees to 50 degrees C
    Storage Temperature
    -20 degrees C to +60 degrees C
    Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
    Certifications
    IBS, CBC, UBC & OSHPD Certified
    Control Panel Enclosure
    NEMA 1 or NEMA 3R, Freestanding Construction
    Low Voltage Standards
    NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
    Operating Temperature
    0 degrees to 50 degrees C
    Storage Temperature
    -20 degrees C to +60 degrees C
    Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Generator Protective Devices

  • ANSI Protective Devices
    15/25, 27/59, 81 O/U, 32, 40, 50, 51
  • Utility Protective Devices

  • ANSI Protective Devices
    15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Equipment

  • Generator Demand Priority Control
    • Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
  • Data Table Interface
    • Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
    • Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • To monitor breaker status, alarms, metering and other operating parameters